FSD-TD Series - Installation Methods

Installations tested to EN1366-2 and classified to BS EN 13501-3*
FSD-TD M2 / DW145 M3

Block/Masonry Wall with Hevac Frame fitted

Single section sizes (mm): 100 x 100 to 1000 x 1000

Tested to EN1366-2 for 4 hours. Equivalent to BS EN 13501-3 classification: ES240 (E240S)
BS EN 1366-2 test/assessment references: 256538/CC261450
Meets the requirement of BS 476-20/22 - refer BS 476-10.6.6.3

Securing of Building Ties:
Either cut 150mm long x 50mm deep pockets into surrounding construction, bend out tabs into pockets and backfill.
Or, Use 5mm dia. steel anchors (Min) and 1.5mm dia. steel wire (Min) around bent-out tabs and anchors to fix to surrounding construction prior to backfill.

* If your proposed installation method has minor variations to that shown above, please confirm acceptance with the local Building Control Authority (BCA) before proceeding. Manufacturers are not able to "approve" specific installation methods.