FSD-TD Series - Installation Methods

Installations tested to EN1366-2 and classified to BS EN 13501-3*
FSD-TD M8

Batt Wall with Batt Frame fitted

Single section sizes (mm): 100 x 100 to 1000 x 1000

Tested to EN1366-2 for 2 hours. Equivalent to BS EN 13501-3 classification: ES120 (E120S)
BS EN 1366-2 test/assessment references: 254506/CC261450
Meets the requirement of BS 476-20/22 - refer BS 476-10.6.6.3

* If your proposed installation method has minor variations to that shown above, please confirm acceptance with the local Building Control Authority (BCA) before proceeding. Manufacturers are not able to "approve" specific installation methods.