FD Series - Installation Methods

Installations tested/assessed to BS EN 1366-2 and classified to BS EN 13501-3*

In Block/Masonry Wall - Hevac Frame Fitted

Single section sizes (mm): 100 x 100 to 1200 x 1000

Tested to BS EN 1366-2 for 4 hours. Equivalent to BS EN 13501-3 Classification: E240
BSEN 1366-2 test/assessment references: 201633/CC 261451
Meets the requirements of BS 476-20/22 - Refer to BS476-10.6.6.3

* If your proposed installation method has minor variations to that shown, please confirm acceptance with the local Building Control Authority (BCA) before proceeding. Manufacturers are not able to "approve" specific installation methods. It is generally accepted that EN 1366-2 tested installations will fulfil any requirements to BS 476-20/22 as the test method is much more severe.

Securing of Building Ties:
Either cut 150mm long x 50mm deep pockets into surrounding construction, bend out tabs into pockets and backfill.
Or, Use 5mm dia. steel anchors (Min) and 1.5mm dia. steel wire (Min) around bent-out tabs and anchors to fix to surrounding construction prior to backfill.

Click on diagram to view larger image

The FD Series installation methods are listed below.


BSB Engineering Services Ltd. reserves the right to modify or withdraw any specification without prior notice that may result from continuous product development. The information contained within this website is for reference only. Full product details should be obtained from our Sales Office.